In the order an engineer does them on a real job.
Read your gauges and thermometer, then type each figure in. Press Enter or tap away to save it.
Tap everything you need for pressure testing, brazing checks and handling refrigerant.
On site, these are the figures you use for this unit.
| Strength test pressure | 48 bar 4.80 MPa |
| Hold strength test | 15 min, no drop |
| Tightness test (PS) | 44 bar 4.40 MPa · hold 30 min |
| Test gas | Oxygen-free nitrogen only |
| Service valves | Keep closed (unit is pre-charged) |
| Evacuation | Below 2 torr, 15 min hold |
Never go above the manufacturer's test pressure. Manuals often give it in MPa: 1 MPa = 10 bar.
You can switch any time with the gauge button at the top of the screen.
Read the needle against the scale. Each small mark is 1 bar.